Voltage inverters
- Trade mark:SBPM-IN
- Series:24 months
- Warranty:IP20...54
- Protection class:Russia
- Country of manufacturing: from 5 to 200 kVA
- Any standard RAL color
- Transformer in the bypass circuit
- Load Distribution Panel
- Earthquake resistance up to 9 points on the MSK-64 scale
- Parallel operation
- An SNMP card for monitoring the Inverter and the power grid
- Direct engine start
- Earthquake resistance up to 9 points on the MSK-64 scale
- User-friendly touch control panel
- Direct engine start
- Transformer in the bypass circuit
The main parameters depend on the type of the Inverter
Nominal output power, kVA | Design | Dimensions (WxDxH), mm | Heat dissipation, not more, W |
5 | СБПМ-ИН-Т-5-380-УХЛ4 | 600х600х2100 | 450 |
10 | СБПМ-ИН-Т-10-380-УХЛ4 | 600х600х2100 | 900 |
15 | СБПМ-ИН-Т-15-380-УХЛ4 | 600х600х2100 | 1 115 |
20 | СБПМ-ИН-Т-20-380-УХЛ4 | 600х800х2100 | 1 807 |
30 | СБПМ-ИН-Т-30-380-УХЛ4 | 600х800х2100 | 2 700 |
40 | СБПМ-ИН-Т-40-380-УХЛ4 | 600х800х2100 | 3 600 |
50 | СБПМ-ИН-Т-50-380-УХЛ4 | 600х800х2100 | 4 500 |
60 | СБПМ-ИН-Т-60-380-УХЛ4 | 800х800х2100 | 5 850 |
80 | СБПМ-ИН-Т-80-380-УХЛ4 | 800х800х2100 | 7 200 |
100 | СБПМ-ИН-Т-100-380-УХЛ4 | 1200х800х2100 | 9 000 |
120 | СБПМ-ИН-Т-120-380-УХЛ4 | 1600х800х2100 | 10 800 |
150 | СБПМ-ИН-Т-150-380-УХЛ4 | 1600х800х2100 | 13 500 |
200 | СБПМ-ИН-Т-200-380-УХЛ4 | 2200х800х2100 | 20 000 |
Detailed parameters
Parameter | Standart value | Optionally |
Nominal input voltage, V | = 220 / 400 | = 110 / 700 |
Allowed deviations of input voltage, % from nominal value | ± 15 | ± 20 |
Bypass line power supply frequency, Hz | 50 ± 5 | 6 / 400 |
Nominal output voltage, V | 3х380 / 3х400 | 3х220 / 3х230 / 1х220 / 1х230 |
Output frequency, Hz | 50 ± 0,1 | 50 ± 0,05 |
Stability of output voltage, % from Unom | ±2 | ±1 |
Overload capability, % from Inom | Under operation from the grid: up to 110% - 20 min, up to 125% - 10 Under operation from the grid: up to 110% - 20 min, up to 125% - 10 min, up to 150% - 1 min, 200% - 30 sec, 250% - 10 sec | |
Output voltage regulation range, % from Unom | ± 2 | ± 1 |
Cross-factor | 3:1 | To 7:1 |
Asymmetric load, % from Inom | Up to 100 | - |
Short circuit, % Inom / msec | 300 / 100 | 700 / 100 |
Efficiency, not less, % | 90 | 95 |
Communication interface | RS 485, Ethernet | RS 232 |
Communication protocol | Modbus RTU, TCP | IEC 60870-5-101 / 61850 |
Availability of "dry" contacts | 4 pcs. (configured) | 8 pcs. |
Indication of equipment operation | Sensor LCD panel | - |
Servicing | One-way | Two-way |
Color | RAL 7035 | Any RAL |
External cables input | From bottom | From top |
Protection degree according to GOST 14254-80 | IP 20 | Up to IP 54 |
Earthquake resistance | 6 points by scale MSK-64 | Up to 9 points by MSK-64 / 20G |
Operation temperature | From 0 to +40°C | From -40 to +45°C |
Climatic design | УХЛ 4 | УХЛ 2 / Т1 — Т3 |
Battery current sensor | Buttery current remote sensor | Buttery internal current sensor |
Monitoring of insulation resistance | - | AC / DC relay of monitoring of insulation resistance |
Base | 100 mm | 200 mm |
Set of spares | for 1 year of operation | for 3 years of operation |